I/O Commands 153
Calibrating Analog Input (Analog/Temperature)
Digital Input
Relay
Analog Input
Calibrating Analog Input (Analog/Temperature)
Calibrate Analog
Reset Calibration
Description Manages the Digital input channel status.
User Level Admin
Syntax
iochannel d1|d2|d3|d4|rts|dtr output activate|deactivate
Option output
Manually activates/deactivates the I/O channel.
Description Manages the Relay output channel status.
User Level Admin
Syntax
iochannel r1|r2 output activate|deactivate
Option output
Manually activates/deactivates the I/O channel.
Description Manages the Analog input channel status.
User Level Admin
Syntax
iochannel a1|a2|a3|a4 clear alarm|min|max
Options alarm
Clears the alarm. Note that if the condition that tripped the alarm still exists, the alarm
will not look like it’s cleared, but will reflect the appropriate alarm level severity.
Alarm Level 0 means that the alarm has not been triggered.
min
Clears the minimum value.
max
Clears the maximum value.
Description Calibrates the Analog input channel. When this command is issued, a script will
automatically start, requesting that the minimum and maximum calibration values be
applied to the requested Analog/Temperature channel. See Calibrating Analog Input in
the IOLAN Users Guide for more information.
User Level Admin
Syntax
iochannel a1|a2|a3|a4 calibrate
Description Resets the calibration to factory defaults.
User Level Admin
Syntax
reset io calibration